Parameter 2: Set the low acceptable frequency for the bypass.
50 Hz system: The setting range is from 46.0Hz to 49.0Hz.
60 Hz system: The setting range is from 56.0Hz to 59.0Hz.
The default value is 46.0Hz/56.0Hz.
Parameter 3: Set an acceptable high frequency for the bypass.
50 Hz: The setting range is from 51.0Hz to 54.0 Hz.
60 Hz: The setting range is from 61.0Hz to 64.0Hz.
The default value is 54.0Hz/64.0Hz.
Parameter 2
:
OPN:
Bypass allowed. When selected, the UPS will run in
Bypass mode depending on the bypass settings
enabled/disabled. FBD: Bypass is not allowed. When selected,
it is not allowed to run in Bypass mode under any
circumstances.
Parameter 3
:
ENA:
Bypass Enable is enabled. When selected, Bypass mode is
enabled.
DIS:
Bypass disabled is disabled. If selected, automatic bypass runs,
but manual bypass is not allowed. Manual bypass means the user
operates the UPS manually for Bypass mode. For example, pressing
the OFF button in AC mode to switch to Bypass mode.