15
l
09: Setting maximum battery discharge time
Interface
Settings
Parameter 3
:
000
~
999
: Maximum discharge time from 0 min. to 999 min. The
UPS will be turned off to protect the battery after discharge time
arrives. The default value is 990 min.
DIS: Disable battery discharge time and backup time will depend
on battery capacity.
l
10: saved
Interface
Settings
Stored
l
11: saved
Interface
Settings
Stored
l
12: saved
Interface
Settings
Stored
l
13: Battery voltage calibration
Interface
Settings
Parameter 2: Select the "Add" or "Sub" function to calibrate the
battery voltage to match the actual battery condition.
Parameter 3: voltage range setting from 0V to 5.7V. The default
value is 0V.
l
14: saved
Interface
Settings
Stored
l
15: Inverter voltage calibration
Interface
Settings
Parameter 2
: You will select
Add
or
Sub
for inverter voltage
calibration
Parameter 3
: Setting the voltage range from 0V to 6.4V. The
default value is 0V.