16: Floating charger Charging voltage adjustment
Interface
Settings
Parameter 2
: You will select
Add
or
Sub
to set the Voltage
adjustment of the floating charger.
Parameter 3
: Voltage range from 0V to 6.4V, Default value 0V.
l
17: Constant charger voltage adjustment
Interface
Settings
Parameter 2
: you will select
Add
or
Sub
to adjust the constant
charger voltage.
Parameter
3: Voltage range from 0V to 3.2V, Default value 0V.
l
18: Setting Maximum charger current
Interface
Settings
Parameter 3
:
The maximum charging current can be adjusted.
The default value is 4A for the long run model and 1A for the
standard model.
The options available are 1A, 2A, 4A and 6A.
The 6A is only available for 16 batteries.
l
19: Grouping and Battery capacity settings
Interface
Settings
Parameter 2
:
Set battery capacity such as 7AH, 9AH, 10AH, 12AH, 17AH, 26AH,
40AH, 65AH, 100AH and so on.
The default value is 9AH.
Parameter 3
:
Set the range of the battery group from 1 to 6. The default value is 1
group. This parameter is for the calculation of battery backup time.
l
20: Backup time calibration
Interface
Settings
Parameter 3
:
Calibrate the displayed backup time by adjusting this multiplier
factor. The formulation is listed below: Displayed backup time =
Actual backup time x Multiplier factor
The default value of the multiplier factor is 1.0 and the setting range
is from 0.5 to 2.