19
Complete Operating Menu / Description
Possible values
Initial value Increment Lower value Upper value Remarks
Max. stroke/minute of 180 1 1 500 off = 0 strokes/min
pumps 1 and 2
D1C2-Cl-022-GB
Access to all setting menus can be blocked with an access code !
Only with pumps for control
pumps
setting ?
dosing pump max.
pump1:
pump2:
control
pump1 chlor
pump2 Dechlor
pulse/minute
180
180
Pumps
D1C2-Cl-023-GB
Access to all setting menus can be blocked with an access code !
only with limit value relay, solenoid valve relay or servomotor
relays
setting ?
solenoid valve 2
dechlor
solenoid valve 1
chlor
period
min. time
10 s
1 s
period
min. time
10 s
1 s
control
solenoid valves:
SV1 chlor
SV2 dechlor
relay adjustment
relay1:
relay2:
SV1
SV2
Relay for power activation
Possible values
Initial value Increment Lower value Upper value Remarks
Relay adjustment as per identity Motor * In the case of “Limit
code Solenoid valve value” - relays remain
(SV1, SV2) active even in the event of
Limit value an error.
(Limit 1/2)*
Actuator 1,2
Timer 1, 2
Servomotor only with servomotor
off
relays
setting ?
timing 1
relay 1
period 1 h
t on: 1 min
timing 2
relay 2
period 1 h
t on: 1 min
with timer
relay adjustment
relay 1: timer
relay 2: timer
D1C2-Cl-034-GB
BA_DM_173_03_09_GB.p65 30.03.2009, 12:10 Uhr19

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ProMinent DULCOMETER D1C and is the answer not in the manual?

ProMinent DULCOMETER D1C Specifications

General IconGeneral
BrandProMinent
ModelDULCOMETER D1C
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals