21
Complete Operating Menu / Description
a) theoretical switching time < min. time:
off
on
t
off
on
t
Cycle
Cycle
Cycle
Cycle
Cycle
Cycle
min. time
min. time
theoretical
actual
The DULCOMETER
®
D1C does not switch for a certain number of cycles until the sum of the theoretical
switching times exceeds the “min. time”. Then the
DULCOMETER
®
D1C
switches for the duration of this
total time
.
b) theoretical switching time > (cycle - min. time) and calculated switching time < cycle
Cycle
min. time
off
on
t
off
on
t
Cycle
Cycle
Cycle
Cycle
Cycle
min. time
theoretical
actual
The DULCOMETER
®
D1C does not deactivate for a certain number of cycles until the differences between
cycle and theoretical switching time exceed the “min. time”.
BA_DM_173_03_09_GB.p65 30.03.2009, 12:10 Uhr21