7.2 Specification of Tower Type UPS 6KVA - 10KVA
50Hz:44Hz~56Hz or 60Hz:54Hz~66Hz
≧
0.99 @ nominal voltage (input voltage)
≤5% (Linear Load), ≤8% (Non-linear Load)
Frequency Range(Line Mode)
Frequency Range (Batt. Mode)
AC Mode: Battery Mode:
30mins @102%-110% load 10min @102%-110% load
10mins @110%-130% load 1min @110%-130% load
30sec @130%-150% load 10sec @110%-130% load
500ms @>150% load 500ms @>150% load
≦
2% THD (Linear Load);
≦
5% THD (Non-linear Load)
2-stage or 3-stage (settable)
Load level, Battery level, AC mode, Battery mode, Bypass mode,and Fault conditions
-15~60℃ (no battery inside)
<1000m ( the height above 1000m should be reduced to a maximum of 4000m.)
Less than 50dBA @ 1 Meter
Standard: RS232, USB; Option: Dry contact, EPO