7.4 Specification of Rack Mount UPS 6KVA - 10KVA
MODEL
6K
6KB
10K
10KB
CAPACITY
6KVA/6KW
10KVA/10KW
Battery Voltage
192V
(default)
/240V
192V
(default)
/240V
Size, DxWxH (mm)
440X420X88
UPS: 440X420X88
Battery Pack:
440X680X88
440X420X88
UPS: 440X420X88
Battery Pack:
440X680X88
Net Weight (kgs)
10
UPS: 10
Battery Pack: 48
11
UPS: 11
Battery Pack: 48
INPUT
Nominal Voltage
208/220/230/240VAC
Input Voltage Range
110-300VAC
Frequency Range
50Hz:44Hz~56Hz or 60Hz:54Hz~66Hz
Phase
Single Phase, L+N+PE
Power Factor
0.99 @ nominal voltage (input voltage)
Harmonic Distortion
≤4% (Linear Load), 5% (Non-linear Load)
OUTPUT
Output voltage
208/220/230/240VAC
AC Voltage Regulation
± 1% (Batt. Mode)
Frequency Range(Line Mode)
Synchronized range
Frequency Range (Batt. Mode)
50 Hz or 60Hz ± 0.1%
Overload Capacity
30mins @102%-110% load
10mins @110%-130% load
30sec @130%-150% load
500ms @>150% load
Current Crest Ratio
3:1
Harmonic Distortion
3% THD (Linear Load);
6% THD (Non-linear Load)
Transfer
Time
AC to Battery
0ms
Inverter to Bypass
0ms
Waveform (Batt. Mode)
Pure Sine Wave
EFFICIENCY
AC Mode
95.5%
Battery Mode
95.3%
BATTERY
MODEL
1K
1KB
2K
2KB
3K
3KB
Storage temperature
-15~60℃ (no battery inside)
Altitude
<1000m ( the height above 1000m should be reduced to a maximum of 4000m.)
Noise Level
Less than 50dBA @ 1 Meter
COMMUNICATION
Communication Interface
Standard: RS232, USB; Option: Dry contact, EPO
Smart Slot
Optional SNMP Card