41
7.5 Specification of Rack Mount Battery Pack
MODEL
72VB
96VB
192VB
240VB
Battery Type
Sealed Maintenance-free
Battery Voltage
72VDC
96VDC
192VDC
240VDC
Size, DxWxH (mm)
440X420X88 [2U]
440X680X88 [2U]
440X600X132 [3U]
Net Weight (kgs)
23
28
48
57
Battery Numbers
6x12V7AH
8x12V7AH
16x12V7AH
20x12V7AH
Charging Current
1A
Charging Voltage
81VDC
108VDC
216VDC
270VDC
Breaker
1P 63A
Output Port
2 x Anderson connector
ENVIRONMENT
Ambient temperature
0- 40°C
Storage temperature
0- 40°C
MODEL
6K
6KB
10K
10KB
Battery Type
Sealed Maintenance-free
Battery Numbers
16
(default)
/20
16x12V7AH
16
(default)
/20
16x12V7AH
Charging Current
5A (Default)
1A-12A adjustable
1A (Default)
1A-12A adjustable
5A (Default)
1A-12A adjustable
1A (Default)
1A-12A adjustable
Charging Voltage
216VDC
Charging Mode
2-stage or 3-stage (settable)
INDICATORS
LCD
UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and
Fault conditions
ENVIRONMENT
Ambient temperature
0- 40°C
Operation Humidity
5%-95% (non-condensing)
Storage temperature
-15~60℃ (no battery inside)
Altitude
<1000m ( the height above 1000m should be reduced to a maximum of 4000m.)
Noise Level
Less than 50dBA @ 1 Meter
COMMUNICATION
Communication Interface
Standard: RS232, USB; Option: Dry contact, EPO
Smart Slot
Optional SNMP Card