13. TERMINALS AND WIRING
The terminals are IP20 finger safe constructed and suitable for field- and factory wiring. Shipped in open position.
Input and output DC-OK-Signal
Type
Bi-stable, quick-connect spring-clamp
terminals
Push-in terminals
Solid wire Max. 6mm
2
Max. 1.5mm
2
Stranded wire Max. 4mm
2
Max. 1.5mm
2
American Wire Gauge AWG 20-10 Max. AWG 28-16
Max. wire diameter 2.8mm (including ferrules) Max. 1.6mm (including ferrules)
Wire stripping length 10mm / 0.4inch 7mm / 0.28inch
Screwdriver Not required Not required
Recommended tightening torque Not applicable Not applicable
Fig. 13-1 Connecting a wire
Instructions:
a) Use appropriate copper cables that are designed for minimum
operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum
90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal
connection!
d) Ferrules are allowed.
11/27
1.
Insert the wire
2.
Close the lever
To disconnect wire:
reverse the procedure
Daisy chaining:
Daisy chaining (jumping from one DC/DC converter output to the next) is allowed as long as the average output
current through one terminal pin does not exceed 25A. If the current is higher, use a separate distribution terminal
block as shown in Fig. 13-3.
Fig. 13-2 Daisy chaining of outputs Fig. 13-3 Using distribution terminals
DC/DC
Converter
+ +
- -
Input
Output
Load
+
-
max 25A!
DC/DC
Converter
+ +
- -
Input
Output
Load
+
-
Distribution
Terminals
DC/DC
Converter
+ +
- -
Input
Output
DC/DC
Converter
+ +
- -
Input
Output
May 2017 / Rev. 0.1 DS-QS10.241-60-EN preliminary