CP10.241-60
CP-Series
24V, 200W, DC/DC CONVERTER
P R E L I M I N A R Y
4. AC-INPUT
Do not operate this DC/DC converter with an AC-input voltage. Use the CP10.241 or CP10.241-C1 (when conformal
coating is needed) unit instead.
5. INPUT INRUSH CURRENT
An active inrush limitation circuit (inrush limiting fixed resistor which is bypassed by a relay) limits the input inrush
current after turn-on of the input voltage.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
DC 96V DC 110V
Inrush current Max. 8A
peak
8A
peak
At 110Vdc, temperature independent
Typ. 2.5A
peak
2.5A
peak
At 110Vdc, temperature independent
Inrush energy Negligible low At 110Vdc, temperature independent
Fig. 5-1 Typical input inrush current behaviour at
nominal load and 25°C ambient
50ms/DIV
Input
current
0.5A/DIV
Input
voltage
20V/DIV
Output voltage 5V/DIV
May 2017 / Rev. 0.1 DS-QS10.241-60-EN preliminary
All parameters are typical values specified at 24V, 8.3A output, 110Vdc input, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany