CP10.241-60
CP-Series
24V, 200W, DC/DC CONVERTER
May 2017 / Rev. 0.1 DS-QS10.241-60-EN preliminary
All parameters are typical values specified at 24V, 8.3A output, 110Vdc input, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
P R E L I M I N A R Y
24.10. MOUNTING ORIENTATIONS
Mounting orientations other than all terminals on the bottom require a reduction in continuous output power or a
limitation in the maximum allowed ambient temperature. The amount of reduction influences the lifetime expectancy
of the DC/DC converter. Therefore, two different derating curves for continuous operation can be found below:
Curve A1 Recommended output current.
Curve A2 Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 24-8
Mounting
Orientation A
(Standard
orientation)
DC/DC
Converter
OUTPUT
INPUT
Output Current
0
20 30 40 50
70°C
2
4
6
8A
60
A
1
Ambient Temperature
8.3A
Fig. 24-9
Mounting
Orientation B
(Upside down)
DC/DC
Converter
OUTPUT
INPUT
Output Current
0
20 30 40 50
70°C
2
4
6
8A
60
A
2
Ambient Temperature
A
1
8.3A
Fig. 24-10
Mounting
Orientation C
(Table-top
mounting)
Output Current
0
20 30 40 50
70°C
2
4
6
8A
60
Ambient Temperature
A
1
A
2
8.3A
Fig. 24-11
Mounting
Orientation D
(Horizontal cw)
DC/DC
Converter
OUTPUT
INPUT
Output Current
0
20 30 40 50
70°C
2
4
6
8A
60
Ambient Temperature
A
1
A
2
8.3A
Fig. 24-12
Mounting
Orientation E
(Horizontal ccw)
DC/DC
Converter
OUTPUT
INPUT
Output Current
0
20 30 40 50
70°C
2
4
6
8A
60
Ambient Temperature
A
1
A
2
8.3A
27/27