CP10.241-60
CP-Series
24V, 200W, DC/DC CONVERTER
P R E L I M I N A R Y
3. DC-INPUT
Use a battery or a similar DC source. A supply from the intermediate DC-bus of a frequency converter is not
recommended and can cause a malfunction or damage the unit.
Input voltage Nom. DC 96-110V -30%/+40%
Input voltage range 67-154Vdc
57-67Vdc Short term for 2s, no start at 57Vdc
Input current Typ. 2.25A At 8.3A and 96Vdc input voltage, see Fig. 3-3
Typ. 1.95A At 8.3A and 110Vdc input voltage, see Fig. 3-3
Allowed voltage between input
to earth (ground)
Max. 300Vdc Continuous, IEC 62477-1
Allowed input ripple voltage Max. 15Vpp
3Vpp
50Hz –10kHz
10kHz – 50kHz
Turn-on voltage Typ. 64.5Vdc Steady-state value, temperature independent, see Fig.
3-1
Shut-down voltage Typ. 62.5Vdc Steady-state value, temperature independent, see Fig.
3-1
Start-up delay Typ. 700ms At 96Vdc input, see Fig. 3-2
Typ. 600ms At 110Vdc input, see Fig. 3-2
Rise time Typ. 45ms At 8.3A constant current load, 0mF load capacitance
Typ. 90ms At 8.3A constant current load, 8mF load capacitance,
see Fig. 3-2
Turn-on overshoot Max. 200mV See Fig. 3-2
External input protection See recommendations in chapter 24.3.
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, definitions
Turn-on
67V
Rated
input range
max.
500ms
V
IN
P
OUT
375Vdc154V
Shut-down
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Input
Voltage
Fig. 3-3 Input current vs. output load at 24V
8
01234
0
0.5
1.0
1.5
2.5
Output Current
Input Current, typ.
567
9A
2.0
3A
(a) 96Vdc,
(b) 110Vdc
(a)
(b)
May 2017 / Rev. 0.1 DS-QS10.241-60-EN preliminary
All parameters are typical values specified at 24V, 8.3A output, 110Vdc input, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/27