CP10.241-60
CP-Series
24V, 200W, DC/DC CONVERTER
P R E L I M I N A R Y
Fig. 6-3 Short-circuit on output, Hiccup
PLUS
mode, typ.
Output
Current
0
11.5A
18s
18s
18s
2s
2s
2s
t
Short -circuit
Normal
operation
Normal
operation
7. HOLD-UP TIME
The internal capacitor, which supplies the energy for the hold-up time is isolated by a diode to the input voltage. A
short on the input line does not discharge the internal hold-up capacitor.
DC 96V DC 110V
Hold-up Time Typ. 89ms 89ms At 4.15A, see Fig. 7-1
Min. 67ms 67ms At 4.15A, see Fig. 7-1
Typ. 45ms 45ms At 8.3A, see Fig. 7-1
Min. 37ms 37ms At 8.3A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions
0
20
40
60
80
100ms
70 90 110 130 150Vdc
Input Voltage
Hold-up Time
at 8.3A, typ.
at 4.14A, min.
at 4.15A, typ.
at 8.3A, min.
- 5%
Hold-up Time
Output
Voltage
Input
Voltage
May 2017 / Rev. 0.1 DS-QS10.241-60-EN preliminary
All parameters are typical values specified at 24V, 8.3A output, 110Vdc input, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted.