CP10.241-60
CP-Series
24V, 200W, DC/DC CONVERTER
P R E L I M I N A R Y
6. OUTPUT
Output voltage Nom. 24V
Adjustment range Min. 24-28V Guaranteed
Max. 30V
*)
At clockwise end position of potentiometer
Factory setting Typ. 24.1V ±0.2%, at full load, cold unit
Line regulation Max. 10mV 67-154Vdc
Load regulation Max. 100mV Static value, 0A Æ 8.3A
Ripple and noise voltage Max. 50mVpp 20Hz to 20MHz, 50Ohm
Output current Nom. 8.3A At 24V, ambient temperature <70°C, see Fig. 6-1
Nom. 7.1A At 28V, ambient temperature <70°C, see Fig. 6-1
Typ. 30A Up to 12ms, output voltage stays above 20V, see Fig.
6-2 and Fig. 24-3, This peak current is available once
every five seconds (firmware controlled).
Output power Nom. 200W Continuously available
Overload behaviour Cont. current Output voltage > 13Vdc, see Fig. 6-1
Hiccup
PLUS
mode
**)
Output voltage < 13Vdc, see Fig. 6-1
Short-circuit current Min. 9.5A
***)
Load impedance 50mOhm, see Fig. 6-1
Max. 13.5A
***)
Load impedance 50mOhm, see Fig. 6-1
Max. 4.3A Average (R.M.S.) current, load impedance 50mOhm,
see Fig. 6-3
Min. 28A Up to 12ms, load impedance 50mOhm, see Fig. 6-2
Typ. 30.5A Up to 15ms, load impedance 50mOhm, see Fig. 6-2
Output capacitance Typ. 4 400μF Included inside the power supply
*) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not a
guaranteed value, which can be achieved. The typical value is 28.6V.
**) Hiccup
PLUS
Mode
At heavy overloads (when output voltage falls below 13V), the power supply delivers continuous output current for 2s. After this, the
output is switched off for approx. 18s before a new start attempt is automatically performed. This cycle is repeated as long as the
overload exists. If the overload has been cleared, the device will operate normally. See Fig. 6-3
***) Discharge current of output capacitors is not included.
Fig. 6-1 Output voltage vs. output current,
typ.
Fig. 6-2 Dynamic output current capability,
typ.
Output Voltage
0
01
4
8
12
28V
16
20
24
0
12A62 4 8
Adjustment
Range
Output Current
Continuous
current
Factory
setting
Hiccup
PLUS
mode
Output Voltage
(dynamic behavior, < 12ms)
0
0
4
8
12
28V
16
20
24
50A2010 30 40515253545
Adjustment
Range
Output Current
May 2017 / Rev. 0.1 DS-QS10.241-60-EN preliminary
All parameters are typical values specified at 24V, 8.3A output, 110Vdc input, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
6/27