CP10.241-60
CP-Series
24V, 200W, DC/DC CONVERTER
P R E L I M I N A R Y
16. ENVIRONMENT
Conformal coating yes All pc-boards are conformal coated
Operational temperature
*)
-40°C to +70°C (-40°F to 158°F) Continuous operation, see Fig. 16-1
+70°C to +85°C (185°F to 185°F) For maximal 10 minutes every hour
Storage temperature -40 to +85°C (-40°F to 185°F) For storage and transportation
Humidity
**)
5 to 95% r.h. IEC 60068-2-30
Vibration sinusoidal 2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
***)
2 hours / axis
IEC 60068-2-6; DC/DC converter in operation
Vibration broadband 1.01grms for 10 minutes; 5-150Hz
***)
IEC 60068-2-64, DC/DC converter in operation;
Tests limits according to EN 61373
Vibration broadband 5.72grms for 300 minutes; 5-150Hz
***)
IEC 60068-2-64, DC/DC converter not in
operation; Tests limits according to EN 61373
Shock 30g 6ms, 20g 11ms, 50g 30ms
***)
3 bumps / direction, 18 bumps in total
IEC 60068-2-27; DC/DC converter in operation
Shock 50g 30ms
***)
3 bumps / direction, 18 bumps in total
IEC 60068-2-27, DC/DC converter not in
operation; Tests limits according to EN 61373
Altitude 0 to 2000m (0 to 6 560ft) Without any restrictions
2000 to 6000m (6 560 to 20 000ft) Reduce output power or ambient
temperature, see Fig. 15-2
IEC 62477-1, overvoltage category II
Altitude de-rating 12W/1000m or 5°C/1000m > 2000m (6500ft), see Fig. 15-2
Over-voltage category III IEC 62477-1, altitudes up to 2000m
II For altitudes from 2000m to 6000m
Degree of pollution 2 IEC 62477-1, not conductive
LABS compatibility The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
*) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit.
**) Do not energize while condensation is present
***) Tested in combination with DIN-Rails according to EN 60715 with a height of 15mm and a thickness of 1.3mm and standard
orientation.
Fig. 16-1 Output current vs. ambient temp. at
24V output voltage
Fig. 16-2 Output current vs. altitude at 24V
output voltage
Allowed Output Current
0
-40 0 20 40
85°C
2
4
6
8
8.3A
10A
60-20 70
A B
Ambient Temperature
A... continuous
B... for maximal 10 minutes
0
0 2000m 4000m 6000m
2
4
6
8
10A
8.3A
Allowable Output Current
Altitude
B
C
A
.
.
.
T
a
m
b
<
7
0
°
C
B
.
.
.
T
a
m
b
<
6
0
°
C
C
.
.
.
T
a
m
b
<
5
0
°
C
A
May 2017 / Rev. 0.1 DS-QS10.241-60-EN preliminary
All parameters are typical values specified at 24V, 8.3A output, 110Vdc input, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
14/27