Pulsafeeder MicroVision - Factory Default Settings

Pulsafeeder MicroVision
43 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
72-910-16 Rev. N
Page 33 of 43
9. Factory Defaults
Parameter
Default
Configuration
Date Format
MM/DD/YY
Time Format
12hr Clock
Water Meter Type
Dry Contact
Water Meter Pulse Volume
100
Water Meter Units
Gallons
Drum Levels
Pumps Run
Display Dampener
1 Second
Rise/Fall Setpoint
Rising
Display Contrast
26
Password
0000(disabled)
Language
English
Settings
Conductivity Setpoint
1500
Conductivity Differential
50
Conductivity Limit Timer
00:00(disabled)
Alarm Setpoint
Track Setpoint/200us
4-20ma Low Range
0
4-20ma High Range
9999
Inhibitor Feed Mode
Limit Timer
Inhibitor Limit Timer
1-hour, 30-minutes
Inhibitor Biocide Tracking
None
Biocide A and B Days/Weeks
All Days/All weeks
Biocide A and B Start Times
00:00(disabled)
Biocide A and B Feed Time
1-minute
Biocide A and B Pre-Bleed Time
00:00(disabled)
Biocide A and B Pre-Bleed Conductivity
Minimum
1475
Biocide A and B Bleed Lockout
00:00(disabled)

Related product manuals