P823 Totaliser Multiplication Factor
Use this parameter if the totaliser increments by to large or small amount,
enter the factor by which the actual flow rate is multiplied by before
incrementing the totaliser.
E.g. if flowrate is being calculated and displayed in ltrs/second and it is
desired to increment the totaliser in cubic metres select 7 = *1000.
When viewing, the totaliser display will state, “Units are: L*1000”, and the
totaliser will be incremented every 1000 litres
Options are:
Totaliser will increment every 1/1000
th
units of flow
Totaliser will increment every 1/100
th
units of flow
Totaliser will increment every 1/10
th
units of flow
Totaliser will increment every 1 units of flow
Totaliser will increment every 10 units of flow
Totaliser will increment every 100 units of flow
Totaliser will increment every 1000 units of flow
Totaliser will increment every 10,000 units of flow
Totaliser will increment every 100,000 units of flow
Totaliser will increment every 1,000,000 units of flow
P824 Totaliser Enable
This parameter determines if the totaliser is enabled or not, the options are
as follows:
Totaliser will be disabled
Totaliser will be enabled