Page 83                                                                                                            
Control  
When P210, 220, 230, 240, 250 = 3 (Control) 
When a relay is being set up as a control relay, the second parameter that 
will be displayed in the menu determines its function.  
P211, P221, P231, P241, P251, Relay Function, 
This function allows the relay to be assigned to specific control functions 
(other than pumps and alarms) several of these functions work in relation to 
time.  
This  can  be  used  to  activate  devices  based  on  elapsed  time  or  running 
cycles, such as a timed rake control to keep a ram lubricated if idle for long 
periods, or penstock/gate operation. 
 
Relay will energise “ON” after the Cycle time that is 
set in Relay Setpoint 2 (P214, 224, 234, 244, 254). 
And turns “OFF”, de-energises, after the On Time 
Period that is set in Relay Setpoint 1 (P213, 223, 
233, 243, 253) 
Step Time Control allows relays to be used to control 
a device, such as a motorised valve or gate, in order to 
maintain the level within two predetermined points. 
Relays will energise “ON” when Step Time condition 
is in effect and de-energises “OFF” when Step Time 
goes off. One relay will be required to control an 
increase in level, (‘open’ the device) and a second 
relay is required to control a decrease in level, (‘close’ 
the device). Alarm ID (P212, 222, 232, 242, 252) is 
used to assign the relay to control either the open or 
close condition. Step Time Control relay requires 
three setpoints. The first set point (P213, 223, 233, 
243, 253) determines the level, at which the relay is to 
be activated, (N.B. level setpoint for open relay, 
increase the level, must be lower than the setpoint 
for the close relay, decrease the level). The relay will 
energise “ON” after the Limit time that is set in 
Relay Setpoint 3 (P215, 225, 235, 245, 255). And 
turns “OFF”, de-energises, after the Drive Period 
that is set in Relay Setpoint 2 (P214, 224, 234, 244, 
254).