Page 84
The third parameter for each relay determines the assignment or
condition of the relay, where required.
When P211, 221, 231, 241, 251 = 2 (Step Time)
If the relay is selected for Step Time, then this parameter is used to assign
the relay to the 0 = Open condition (increase level) or 1 = Close condition
(decrease level).
The fourth parameter, fifth parameter and sixth parameter are set to
determine the switch points, “ON” and “OFF” for the relay and where
required the order of start. See control function, table (P211, 221, 231) for
further information.
When P211, 221, 231, 241, 251 =1 (Time)
P213, P223, P233, P243, P253 Relay Setpoint 1
This parameter determines the “Time Period ” that the relay will remain “ON”.
Relay Setpoints are entered in Minutes.
See the appropriate relay Function tables (P211, 221, 231, 241, 251) for further
information.
P214, P224, P234, P244, P254 Relay Setpoint 2
This parameter determines the “Cycle Time ” for the operation of the relay.
See the appropriate relay Function tables (P211, 221, 231, 241, 251) for further
information.
When P211, 221, 231, 241, 251 = 2 (Step Time)
P213, P223, P233, P243, P253 Relay Setpoint 1
Relay Setpoint 1 is entered in values of Measurement Units (P104)
See the appropriate relay function tables (P211, 221, 231, 241, 251) for further
information.
P214, P224, P234, P244, P254 Relay Setpoint 2
Relay Setpoints are entered in Seconds to set Drive Period, the time that the
relay will remain ON
See the appropriate relay Function tables (P211, 221, 231, 241, 251) for further
information.