Page 34
Wait …..
Parameter
Default
Description
P101
Transducer
1 = dB3
Type of Transducer to be used.
P706
Volume Units
6 = Mil. USG
Units of flow as on display and used
for calculations.
1=litres
3=cubic feet
5=US gallons
2 = cubic metres
4 = UK gallons
6 = Mil.USG
P707
Time Units
4 = per day
Units of time that volume units will
be displayed and calculated in.
1= units/sec.
3= units/hour
2= units/min.
4= units/day
P104
Measnt Units
5 = inches
Units used to enter dimensions, and
displayed where appropriate.
1 = metres
3 = millimetres
5 = inches
2 = centimetres
4 = feet
P105
Empty Level
106.299
inches
Distance from the face of the
transducer to the material at the
bottom of the measuring element.
P703
Minimum
Head
0.000 inches
Distance from empty point (P105) to
zero flow.
P704
Max Head
101.378
inches
Distance from zero flow to max
flow. It should be noted that any
change to P704 updates P106 Span
and vice versa.
P824
Totaliser
Enable
1=On
Enables the flow totaliser, P820,
options are 0=Off, 1=On. Note this
totaliser can be viewed during run
via the totaliser “Hot Key” It can be
reset but only via P820, whilst in
“program mode”.
P816
Totaliser ( R )
0=No
Enables the totaliser to be displayed
in the auxiliary display whilst in “run
mode”. Note this totaliser is
“resettable”, whilst in “run mode”,
via the totaliser hot key.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pulsar FlowCERT LITE and is the answer not in the manual?

Pulsar FlowCERT LITE Specifications

General IconGeneral
BrandPulsar
ModelFlowCERT LITE
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals