M-Controller II System Operation Manual - 35 -
84350-201-001 Rev C
Byte count: 86H
Slave ID: 82H
Run Indicator status: FFH (always ON)
Software Version: (2 Bytes) major version first
Controller Serial Number (2 Bytes) high byte first
Special Gas Type [8][3] (24 Bytes) 8 Special Gas Type
Special Unit [8][3] (24 Bytes) 8 Special Unit
Gas Type (40 Bytes) Sensor 0 first, plus 8CH A_In
Unit of Measure (40 bytes) Sensor 0 first, plus 8CH A_In
CRC check: xxxxH
Note:
1). Slave ID = 80H for M-Controller
Slave ID = 82H for M-Controller II
Slave ID = 42H for Q4-Controller II
2). Each Special Gas Type or Special Unit is composed of 3 characters.
3). Gas type and Units Definition:
Value Gas Type Units
00H O2 %Vol
01H CO PPM
02H CO2 %LEL
03H H2S UNITS
04H SO2 Special Unit 1
05H NO Special Unit 2
06H NO2 Special Unit 3
07H Hydrogen Special Unit 4
08H HCN Special Unit 5
09H HCL Special Unit 6
0AH NH3 Special Unit 7
0BH MMH Special Unit 8
0CH O3
0DH C2H4O
0EH Cl2
0FH ClO2
10H CH4
11H C3H8
12H H2
13H Others
14H Special Gas Type 1
15H Special Gas Type 2
16H Special Gas Type 3
17H Special Gas Type 4
18H Special Gas Type 5
19H Special Gas Type 6
20H Special Gas Type 7
21H Special Gas Type 8