Chapter 11: System Specifications
DXi6900 Environmental Specifications
Quantum DXi6900 User’s Guide 393
AverageACCurrent Node 468 Watts, 4.7A @100 VAC 1597 BTU/hr
468 Watts, 1.9A @240 VAC 1597 BTU/hr
Array Module (RBOD) 276 Watts, 2.8A @100 VAC 942 BTU/hr
276 Watts, 1.2A @240 VAC 942 BTU/hr
Expansion Module (EBOD) 168 Watts, 1.8A @100 VAC 780 573 BTU/hr
168 Watts, 0.8A @240 VAC 780 573 BTU/hr
InrushPeakACCurrent Maximum Configuration 59A @ 100 VAC 25A @ 240 VAC
DXi6900 Environmental Specifications
DXi6900 Environmental Specifications
DXi6900ClimaticEnvironment
Temperature Operating 10° to 35°C (5 to 95°F) with a maximum temperature gradient of
10°C per hour
Note:35°C (95°F) is the maximum temperature for the
DXi6900 at sea level. For every 1,000 feet (305 meters) of
altitude, the maximum temperature is reduced by 0.9°C.
Shipping and storage 20° to 60°C (4° to 140°F) with a maximum temperature gradient
of 20°C per hour
Relativehumidity Operating 20% to 80% (non-condensing) with a maximum humidity gradient
of 10% per hour
Shipping and storage 5% to 95% (non-condensing) with a maximum humidity gradient
of 10% per hour
Altitude Operating 16m to 3048 m (–50 to 10,000 ft)
Shipping and storage 16m to 10,600 m (–100 to 35,000 ft)
DXi6900VibrationandShock