UL/cUL approval
Compressor type I (1) Max. fuse (1) I (2) Max. fuse (2)
K5/
HRC form II
K5/
HRC form II
V Hz A A A A
QGD 50 230 60 352.2 400 362.6 400
QGD 50 380 50 218.8 250 222.9 250
QGD 50 380 60 221.4 250 226.2 250
QGD 50 460 60 182.4 200 188.8 225
QGD 50 575 60 145.9 160 151.6 175
UL/cUL approval
Compressor type I (1) Max. fuse (1) I (2) Max. fuse (2)
K5/
HRC form II
K5/
HRC form II
V Hz A A A A
QGD 60 230 60 440.8 500 451.2 500
QGD 60 380 50 260.8 300 264.9 300
QGD 60 380 60 267.5 300 272.3 300
QGD 60 460 60 222.2 250 228.6 250
QGD 60 575 60 176.6 200 182.3 200
I: current in the supply lines at maximum load and nominal voltage
(1): compressors without integrated dryer
(2): compressors with integrated dryer
Fuse calculations for cUL and UL: The indicated fuse size is the maximum fuse size in order to
protect the motor against short circuit. For cUL fuse HRC form II, for UL fuse class RK5.
Possible configurations
There are 3 possible cabling layouts:
• (1): Single supply cables.
• (2): Parallel supply cables