nVent.com | 18
4.2 CONSOLE MODE MENUS
The Console Mode Menu Index below shows all user interface parameters. This menu
shows the Factory Default along with the associated range. The section column refers to
the section in this manual that illustrates the actual keystrokes required to input the
parameters.
Menu #
Section
Menu
Defaults
1
4.2.1
Tag =
00261439
2
4.2.2
Units =
Imperial
3
4.2.3
Switch Control Mode
ON /OFF
4
4.2.4
Control Setpoint =
40’F
5
4.2.5
Deadband =
5’F
6
4.2.6
PASC Setup
…
7
4.2.7
LO TS 1 = LO TS 2 =
DIS
8
4.2.8
LO TS 1 = LO TS 2 =
35’F
9
4.2.9
HI TS 1 = HI TS 2 =
DIS
10
4.2.10
HI TS 1 = HI TS 2 =
180‘F
11
4.2.11
TS 2 Fail =
DIS
12
4.2.12
TS 1 HI LIMIT = TS 2 HI LIMIT =
TS 1 HI LIMIT Setpoint = TS 2 HI LIMIT Setpoint =
TS 1 HI LIMI Alarm = TS 2 HI LIMI Alarm =
DIS
200’F
DIS
13
4.2.13
LO Load =
ENA
14
4.2.14
LO Load =
1.0 A
15
4.2.15
Load Defaults
No
16
4.2.16
HI GFI =
20 mA
17
4.2.17
GFI Trip =
30 mA
18
4.2.18
TS Fail Mode =
ON
19
4.2.19
TS CTL Mode =
TS 1 – FAIL ON
20
4.2.20
OVERRIDE Source =
Ext.
Input =
Remote
Not Used
21
4.2.21
Version
V4.04.3
22
4.2.22
Passcode =
0
23
4.2.23
Communication Setup
HTCbus
24
4.2.24
Auto-Cycle =
DIS
25
4.2.25
Auto-Cycle Interval =
8
26
4.2.26
Auto-Cycle Units =
Hours
27
4.2.27
Contactor Count =
200000
28
4.2.28
Alarm Output =
N.C.
29
4.2.29
Acknowledging/Resetting Alarms
N/A
30
4.2.30
Alarm Output Normal State
Normally Closed