EasyManua.ls Logo

Raychem C910-485 - 1.3 Product Specification: General & Approvals; 1.3 Product Specification: Control & Monitoring

Raychem C910-485
54 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
nVent.com | 5
Exclusive Remedies
The remedies provided herein are the buyer’s sole and exclusive remedies. nVent shall
not be liable for any direct, indirect, special, incidental, or consequential damages,
whether based on contract, tort, or any other legal theory.
Conducted and Radiated EmissionsFCC/DOC Statement of Compliance
This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to Part 15 of the FCC rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a
commercial environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference, in which case the
user will be required to correct the interference at their expense. This equipment does not
exceed Class A limits for radio emissions as set out in Schedule V to VIII of the Radio
Interference Regulations of Communication Canada.
1.3 PRODUCT SPECIFICATION
General
Area of use
Nonhazardous locations
Approvals
Supply voltage
100 V to 277 V, +5/10%, 50/60 Hz
Common supply for controller and heat
-tracing circuit
Enclosure
Protection
NEMA 4X
Materials
FRP/Polycarbonate
Ambient operating temperature
range
40°F to 140°F (–40°C to 60°C)
Ambient storage temperature
range
40°F to 185°F (40°C to 85°C)
Relative humidity
0% to 90%, noncondensing
Control
Relay type
Double-pole, mechanical
Voltage, maximum
277 V nominal, 50/60 Hz
Current, maximum
30 A @ 104°F (40°C) derated to 20 A @ 140°F (60°C)
Control algorithms
EMR: On/off, proportional ambient sensing control
(PASC)
Control range
0°F to 200°F (18°C to 93°C)

Table of Contents