It is recommended to use purified water.
In order to prevent mould growing that may lead to pipe blockage, we recommend to add
alcohol about 10% of the total volume.
If the product is used in an environment that ambient temperature is between -10 and
0, we recommend to use 30% alcohol, and replace it every two months.
If the product is used in an environment that ambient temperature is below -10, please
to use dual-system chillers (with heating function) and ensure uninterrupted operation of
the cooling system.
(2) Requirements for output cable cooling system:
Rate of liquid flow: 1.7-2.0 L/min;
Pressure of liquid flow: < 0.6 MPa at the inflow;
Type of liquid exchange junction: SMC MS-5H-6:
Type of tube: outer diameter 6; inner diameter 4;
Direction of cooling liquid: unidirectional; connect the tube with the water-pipe strictly
according to direction shown on the layer of the tube;
Type of liquid: de-ionized water, condensed water, pure water;
PH value of liquid: 5.5-9;
Filter is needed for the cooling system, and the size of the solid residual practical should
be within 100um;
Maximum temperature of liquid: 45:
Minimum temperature of liquid: greater than the saturated dew-point 5;
Additive to the liquid: satisfies the requirements of PH value and size of solid residual
practical as above;
Radius of the bending of the armored pipe: off-work state (i.e. transportation and
reservation): minimum radius of bending 20 cm; in-work state: minimum radius of
bending 30 cm;