Configure Module 1 - Input Parameters (1-IN) P48
Display Parameter
Range and Units
(Factory Setting)
Description/
Comments
tYPE Input Type VOLt - Voltage
Curr - Current
(Curr)
dCPt
Decimal Point 0, 0.0, 0.00, or 0.000
(0.0)
If 0.000 is selected,
scaling points must be
a positive value.
rnd Rounding
Increment
1, 2, 5, 10, 20, 50, or
100
(0.1)
Used in conjunction
with filtering to
stabilize the display
reading.
FLtr Digital Input
Filtering And
Display Update
0to4
(1)
Increase number for
more filtering effect.
4 = 500 msec display
update rate. Adjusted
by Auto-Tune.
dSP1 Scaling Point #1
Display Value
-999 to 9999
(0.0)
Key-in display low
value.
InP1 Scaling Point #1
Input Signal
0/4-20 mA DC
0-10 VDC
0.00 to 20.00 mA
0.00 to 10.00 V
(4.00)
Press D button to
select Signal Input
method.
Value Key-in
Method
Key-in input low value.
Signal Input
Method
Apply input low value.
dSP2 Scaling Point #2
Display Value
-999 to 9999
(100.0)
Key-in display high
value.
Display Parameter
Range and Units
(Factory Setting)
Description/
Comments
InP2 Scaling Point #2
Input Signal
0/4-20 mA DC
0-10 VDC
0.00 to 20.00 mA
0.00 to 10.00 V
(20.00)
Press D button to
select Signal
Input method.
Value Key-in
Method
Key-in input low
value.
Signal Input
Method
Apply input low
value.
SPLO Setpoint Lower
Limit
-999 to 9999
(0.0)
Set low limit
below high limit.
SPHI Setpoint Upper
Limit
-999 to 9999
(999.9)
Set high limit
above low limit.
SPrP Setpoint Ramp
Rate
0 to 9999 units/minute
(0.0)
0.0 is off (no
ramping).
InPt User Input * PLOC - Program disable
ILOC - Integral action on/off
trnF - auto/manual select
SPrP - Setpoint ramp on/off
ALrS - Reset alarm output(s)
SP2 - Select SP1/SP2
rSP - Select
Local/Remote
PrNt - Serial block print
(PLOC)
Low = lock
Low = off
Low = manual
Low = end ramp
Low = reset
Low = SP2
Low =remote
Low =block print
* Model Number Dependent
-22-
These tables are only used for programming the P48 models. Use
the tables on page 21 if you are programming a T48.