EasyManua.ls Logo

red lion T48 - Module 2: Output Parameters (2-OP); Output Parameters (2-OP)

red lion T48
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configure Module 2 - Output Parameters (2-OP)
Display Parameter
Range and Units
(Factory Setting)
Description/
Comments
CYCt Time
Proportioning
Cycle Time
0 to 250 seconds
(2)
0 turns O1 off. Set to
zero for Linear DC
output control. Not used
for ON/OFF Control.
OPAC Output Control
Action
drct - cooling
rEv - heating
(rEv)
For both PID & ON/OFF
control.
OPLO Output Power
Lower Limit
(Not used in
Manual Control)
0% to 100%, O1
(0)
Set OPLO < OPHI
-100% to 100%,
O1 & O2
(-100)
Negative % is only valid
for O2 cooling control.
OPHI Output Power
Upper Limit
(Not used in
Manual Control)
0% to 100%, O1
(100)
Set OPHI > OPLO
-100% to 100%
O1 & O2
(100)
Negative % is only valid
for O2 cooling control.
OPFL Sensor Fail
Power Level
(Not used in
Manual Control)
0% to 100%, O1
(0)
Select a level to safely
control the process in
the event of input
sensor failure. T48 only.
-100% to 100%
O1 & O2
(0)
OPdP Output Power
Dampening
(filtering) Time
0 to 250 seconds
(3) T48
(1) P48
0 = off (no dampening)
Set in range of 1/50 to
1/10 of integral time.
Adjusted by Auto-Tune.
Display Parameter
Range and Units
(Factory Setting)
Description/
Comments
CHYS ON/OFF Control
Hysteresis
1to250
(2) T48
(0.2) P48
For O1 ON/OFF
Control. Change to
Factory Setting prior
to Auto-Tune.
tcOd Auto-tune
Dampening Code
0to2
(0)
0 = fastest response
2 = slowest response
ANtP Main Linear DC
Output Range *
0to10V
0to20mA
4to20mA
(4 to 20 mA)
Set linear output
range jumper to
match.
ANAS Main Linear DC
Output Source *
OP
InP
SP
(OP)
SP = Active Setpoint
ANUt Main Linear DC
Output Update *
0 to 250 secs
(0)
0 = Update rate of 0.1
sec.
ANLO Main Linear DC
Output Low Scaling
Value *
-999 to 9999
(0.0)
Value depends on
ANAS assignment.
ANHI Main Linear DC
Output High
Scaling Value *
-999 to 9999
(100.0)
Value depends on
ANAS assignment.
* Model Number Dependent
-23-

Table of Contents