Configure Module 7 - Remote Setpoint Parameters (7-rS or
7-n2)
Controller returns to configuration access point (CnFP NO) if remote
setpoint option is not installed.
Display Parameter
Range and Units
(Factory Setting)
Description/
Comments
dSP1 Remote setpoint
display scaling point
#1
-999 to 9999
(0) T48
(0.0) P48
Remote setpoint
display low value.
INP1 Remote setpoint
input scaling point
#1.
0.00 to 20.00 mA
(4.00)
Key in input low
value or Press D to
select Signal Input
method.
dSP2 Remote setpoint
display scaling point
#2
-999 to 9999
(1000) T48
(100.0) P48
Remote setpoint
display high value.
INP2 Remote setpoint
input scaling point
#2
0.00 to 20.00 mA
(20.00)
Key in input low
value or Press D to
select Signal Input
method.
FLtr Remote setpoint
filter time constant
0 to 25 seconds
(2)
0=off
bAnd Remote setpoint
filter band
0to250
(5)
0 = filter always
engaged.
trnF Remote/Local
setpoint transfer
options
nor - normal
Auto - Automatic
trAC - Tracking
(nor)
Auto = Bumpless,
other modes may
bump.
Configure Module 7 - Heater Current Parameters (7-HC or
7-n2)
Controller returns to configuration access point (CnFP NO) if heater
current option is not installed.
Display Parameter
Range and Units
(Factory Setting)
Description/
Comments
Hcur Heater current
transformer scaling
0.0 to 999.9 Amps
(40.0)
Set scaling equal to
primary rating of CT.
Configure Module 8 - Second Linear DC Analog Output (8-A2)
Controller returns to Configuration Access Point (CnFP-NO) if second
linear DC analog option is not installed.
Display Parameter
Range and Units
(Factory Setting)
Description/
Comments
A2tP Second linear DC
output range
0to10V
0to20mA
4to20mA
(4-20)
Set Secondary
Output jumper to
match.
A2LO Second linear DC
output low scaling
value
-999 to 9999
(0) T48
(0.0) P48
Corresponding temp
or process value for
low output.
A2Hl Second linear DC
output high scaling
value
-999 to 9999
(1000) T48
(100.0) P48
Corresponding temp
/processvaluefor
high output.
Configure Module 9 - Factory Service Operations (9-FS)
Display Parameter
Range and Units
(Factory Setting)
Description/
Comments
CodE Factory service
function code.
48 - Calibrate
instrument
Refer to Calibration
Section for details.
66 - Reset
parameters to factory
settings
77- (twice in
succession) Reset
controller calibration
to nominal values
(Caution: This
operation results in
up to ±10% reading
error.)
-28-