Calibration For P48
When re-calibration is required (generally every two years), this procedure
should be performed by qualified technicians using appropriate equipment.
Equipment source accuracy of 0.03% or better is required.
The procedure consists of applying accurate voltage and current signals.
Allow a 30 minute warm-up period before starting this procedure.
This procedure may be aborted by disconnecting power to the controller
before exiting the configuration mode. The existing calibration settings
remain in effect.
Factory Service Operations (9-FS)
Display Parameter Range Description/Comments
CodE Enter factory service
function code
48 Calibrate Instrument
CAL Input calibration yes/no Calibration for both voltage and
current.
A1CL Main Linear DC Output
calibration
yes/no Model number dependent.
Calibrate either 10 V or 20 mA.
A2CL Second Linear DC
Output calibration
yes/no Model number dependent.
Calibrate either 10 V or 20 mA.
n2CL Remote Setpoint
Calibration
yes/no Model number dependent
Input Calibration
Connect voltage calibration source with an accuracy of 0.1% or better.
Display Action Description/ Comments
StP1 Apply 0.0 V Wait 10 seconds press P.
StP2 Apply 2.5 V Wait 10 seconds press P.
StP3 Apply 5.0 V Wait 10 seconds press P.
StP4 Apply 7.5 V Wait 10 seconds press P.
StP5 Apply 10 V Wait 10 seconds press P.
Connect current calibration source with an accuracy of 0.1% or better.
StPA Apply 0 mA Wait 10 seconds press P.
StPB Apply 20 mA Wait 10 seconds press P.
Main or Second Linear DC Analog Output Calibration
1. Set the Linear DC Output jumper for the range to be calibrated. (See Linear
DC Analog Output Jumper Selection, page 12).
2. Connect a meter with an accuracy of 0.05% or better to output.
3. For each step, use the controller arrow keys to adjust the external meter
display to match the parameter being calibrated. Press P when the output
is correct, or if the parameter is not being calibrated.
Display Parameter External Meter Action
C 0V 0 V Calibration 0.00 Adjust if necessary, press P.
C 10V 10 V Calibration 10.00 Adjust if necessary, press P.
C 0c 0 mA Calibration 0.00 Adjust if necessary, press P.
C 20c 20 mA Calibration 20.00 Adjust if necessary, press P.
Remote Setpoint Calibration
Connect DC mA source with an accuracy of 0.03% or better.
Display Action Description/Comments
StP1 Apply 0 mA Wait 10 seconds, press P.
StP2 Apply 5 mA Wait 10 seconds, press P.
StP3 Apply 10 mA Wait 10 seconds, press P.
StP4 Apply 15 mA Wait 10 seconds, press P.
StP5 Apply 20 mA Wait 10 seconds, press P.