Configure Module 6 - Serial Communications (6-SC)
Controller returns to configuration access point (CnFP NO) if RS485 serial
option is not installed.
Display Parameter
Range and Units
(Factory Setting)
Description/
Comments
bAUd Baud rate 300 to 9600
(9600)
Baud rate of unit
must match
connected
equipment.
ConF Character Frame
format
7O1
7E1
7n2
8n1
(7O1)
7 data, odd parity, 1
stop (was odd)
7 data, even parity, 1
stop (was even)
7 data, no parity, 2
stop (was none)
8 data, no parity, 1
stop
Addr Controller address 0 to 99
(0)
For multiple unit
applications, each
unit must have a
unique node address.
Abrv Abbreviated or full
transmission
yes/no
(no)
Selecting yes, the
controller does not
transmit mnemonics.
PoPt Print options yes/no
(no)
Selecting yes allows
print options shown
below, to be
programmed.
INP Input yes/no
(yes)
SEt Setpoint yes/no
(yes)
OPr % Output Power yes/no
(yes)
Pbd % Proportional Band yes/no
(no)
INt Integral Time yes/no
(no)
Display Parameter
Range and Units
(Factory Setting)
Description/
Comments
dEr Derivative Time yes/no
(no)
AL1 Alarm 1 * yes/no
(no)
AL2 Alarm 2 * yes/no
(no)
dEv Deviation From
Setpoint *
yes/no
(no)
OFP % Output Power
Offset
yes/no
(no)
r-P Setpoint Ramp Rate yes/no
(no)
Crg Relative Gain yes/no
(no)
Cdb Deadband yes/no
(no)
OSt Output Status yes/no
(no)
rSP Remote Setpoint * yes/no
(no)
HCr Heater Current * yes/no
(no)
* Model Number Dependent
-27-