Common Mode Rejection: Greater than 120 dB, DC to 60 Hz
Protection: Input overload 120 VAC max. for 15 sec. max.
6. T48 INDICATION ACCURACY: ±(0.3% of Span +1°C) Includes NIST
conformity, cold junction effect and A/D conversion errors at 23°C after
20 min. warm-up.
7. THERMOCOUPLE INPUT (T48 only):
Types: T, E, J, K, R, S, B, N, Linear mV, Software selectable
Input Impedance: 20 MW, all types
Lead resistance effect: 0.25 mV/W
Cold junction compensation: Less than ±C (±1.C max.) error over 0 to
50°C max. ambient temperature range. Defeated for Linear mV
indication mode.
Resolution: 1° for all types, or 0.1° for T, E, J, K and N only.
TC TYPE RANGE
WIRE COLOR
ANSI BS 1843
T -200 to +400°C
-328 to +752°F
(+) blue
(-) red
(+) white
(-) blue
E -200 to +750°C
-328 to +1382°F
(+) violet
(-) red
(+) brown
(-) blue
J -200 to +760°C
-328 to +1400°F
(+) white
(-) red
(+) yellow
(-) blue
K -200 to +1250°C
-328 to +2282°F
(+) yellow
(-) red
(+) brown
(-) blue
R 0 to +1768°C
+32 to +3214°F
(+) black
(-) red
(+) white
(-) blue
S 0 to +1768°C
+32 to +3214°F
(+) black
(-) red
(+) white
(-) blue
B +149 to +1820°C
+300 to +3308°F
(+) grey
(-) red
(+) none
(-) blue
N -200 to +1300°C
-328 to +2372°F
(+) orange
(-) red
(+) orange
(-) blue
mV -5.00 to +56.00 no standard no standard
8. RTD INPUT (T48 only): 2 or 3 wire, 100 W platinum, alpha = 0.00385
(DIN 43760), alpha = 0.0039162
Excitation: 150 mA typical
Resolution: 1 or 0.1 degree
Lead Resistance: 15W max. per input lead.
RTD TYPE RANGE
385 -200 to +600°C
-328 to +1100°F
392 -200 to +600°C
-328 to +1100°F
OHMS 1.0 to 320.0
9. P48 RANGE AND ACCURACY:
Input
Range
Accuracy*
(18 to 28°C)
Accuracy*
(0 to 50°C)
Impedance
Max.
Continuous
Overload
Resolution
10 VDC
(-1 to 11)
0.10% of
reading
+0.02 V
0.30% of
reading
+0.03 V
1M ohm 300 V 10 mV
20 mA DC
(-2 to 22)
0.10% of
reading
+0.03 mA
0.30% of
reading
+0.04 mA
10 ohm 100 mA 10 uA
* Accuracies are expressed as ± percentages after 20 minute warm-up. The
controller’s accuracy is specified in two ways: Accuracy over an 18 to
28°C range at 10 to 75% RH environment; and accuracy over a 0 to 50°C
range at 0 to 85% RH (non-condensing) environment. Accuracy over the
wide sensor range reflects the coefficient of the internal circuitry.
10. USER INPUT: Internally pulled up to +5 VDC (1 MW). V
IN
MAX = 5.25
VDC; V
IL
= 0.85 V max; V
IH
= 3.65 V min; I
OFF
= 1 mA max.
Response time: 120 msec max
Functions: Program Lock
Integral Action Lock
Auto/Manual Mode Select
Setpoint Ramp Enable
Reset Alarms
Local/Remote Setpoint Select
Setpoint 1/Setpoint 2 Select
Serial Block Print
-77-