17. HEATER CURRENT MONITOR INPUT (T48 only): (optional)
Type: Single phase, full wave monitoring of load currents controlled by
main output (01)
Input: 100 mA AC output from current transformer (RLC #CT004001) or
any CT with 100 mA AC output.
Display Scale Range: 1.0 to 999.9 Amps or 0.0 to 100.0%
Input Resistance: 5 W
Accuracy:
At 25°C range: +(0.5% of full scale + 1/2 LSD), (5 to 100% of range)
Over 0 to 50°C range: ±(1.0% of full scale +1/2 LSD), (5 to 100% of
range)
Frequency: 50 to 400 Hz
Alarm Mode: Dual acting: heater element fail detect and control device fail
detect
Overange: 105% Capacity
Overload: 200 mA (Continuous)
18. SERIAL COMMUNICATIONS: (optional)
Type: RS485 multipoint, balanced interface
Baud Rate: 300 to 9600
Data Format: 7 data bits, odd, even or no parity, 1 stop bit
Node Address: 0-99, max of 32 units per line
Transmit Delay: 2-100 msec or 100-200 msec
Data Encoding: ASCII
Isolation w.r.t Main Input Common: 500 Vrms for 1 min. (50 V working)
Not isolated w.r.t. Remote Setpoint or Heater Current inputs, or Analog
Output common
Note: RS485 and the Analog Output commons are not internally isolated
within the controller. The terminating equipment of these outputs must
not share the same common (i.e.. earth ground).
19. ISOLATION BREAKDOWN RATINGS:
AC line with respect to all Inputs and outputs: 250 V working (2300 V for 1
minute).
Main input with respect to Analog Outputs, Remote Setpoint Input, Heater
Current Input: 50 V working (2300 V for 1 minute).
All other inputs and outputs with respect to relay contacts: 2000 VAC
Not isolated between Analog Outputs, Remote Setpoint and Heater
Current commons.
20. CERTIFICATIONS AND COMPLIANCES:
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
IEC/EN 61010-1
RoHS Compliant
UL Recognized Component: File #E179259
Type 4X Enclosure rating (Face only)
IP65 Enclosure rating (Face only)
IP20 Enclosure rating (Rear of unit)
Refer to the EMC Installation Guidelines section of the manual for additional
information.
21. ENVIRONMENTAL CONDITIONS:
Operating Range: 0 to 50°C
Storage Range: -40 to 80°C
T48 Span Drift (maximum): 130 ppm/°C, main input
T48 Zero Drift (maximum): 1 mV/°C, main input
Operating and Storage Humidity:
85% max. relative humidity (non-condensing) from 0°C to 50°C.
Vibration to IEC 68-2-6: Operational 5 to 150 Hz, 2 g.
Shock to IEC 68-2-27: Operational 20 g (10 g relay).
Altitude: Up to 2000 meters
22. CONNECTION: Wire clamping screw terminals
23. CONSTRUCTION: Black plastic alloy case and collar style panel latch.
Panel latch can be installed for vertical or horizontal instrument stacking.
One piece tinted plastic bezel. Bezel assembly with circuit boards can be
removed from the case to change the output board without removing the
case from the panel or disconnecting wiring. Unit meets NEMA 4X/IP65
requirements for indoor use when properly installed. Installation Category
II, Pollution Degree 2.
24. WEIGHT: 0.38 lbs (0.17 kgs)
-79-