Corrigo E Heating manual, revision G Chapter 8 Configuration 31
Actuator run time
HS1: 255 sec
HS2: 255 sec
HS3: 255 sec
Actuator run time
HW1: 80 sec
HW2: 80 sec
8.9 Valve exercising
The valves can be exercised once daily. Default time is 3:00 pm but can be set to any time. The
actuators will be forced to either endpoint for the set actuator running time. The pumps will run and
the temperature offset alarm will be blocked for the duration of the exercising.
Actuator exercise
HS1: Off
Hour for exerc.: 15
Minute for ex.: 00
8.10 Leakage monitoring
Once a week, the control valves will be closed and the energy usage measured for a preset time. An
alarm is generated should the energy leakage be larger than a settable value, default 3.0 kW.
The time for and duration of the leakage monitoring is settable. Default is Sundays at 2:00 am for 30
minutes.
Leakage mon:Off
Weekday:Sunday
Hour: 2
Duration: 30 min
Permitted leakage
3.00 kW
Start monitoring now
No
8.11 Pulse inputs
Energy pulse heating
100.0 kWh/Pulse
Volume pulse heating
10.0 liters/Pulse
Cold water 1
10.0 liters/Pulse
Cold water 2
10.0 liters/Pulse
Electric meter
100.0 kWh/Pulse