Corrigo E Heating manual, revision G Chapter 8 Configuration 34
8.13 Other parameters
A collection of different parameters that did not fit into any of the other menus.
8.13.1 Building inertia and boost
For detailed information, see 5.1.7 Building inertia and boost.
The building inertia is settable to one of three levels: None, Medium or High.
The displacement is calculated as follows:
Displacem.=Factor*(17 - outd. temp)*night set-back
Where Factor is a settable factor 0…10 where 0 gives no boost and 10 gives maximum boost.
Boost duration time is calculated as below:
Time=1.6*(17 - outdoor temp)
Building inertia
None
Boost factor (0-10)
1
8.13.2 Power limitation
Using a digital input the power to the heating systems can be temporarily restricted. When activated,
the setpoints are lowered by a settable factor (% relative to 20°C). The limitation applies to all
configured heating systems. The limitation is calculated as below:
Limited setpoint=20+(Setpoint-20)*Factor/100
Power limitation
100% rel +20°C
Factor 100 gives no setpoint lowering, 0 gives full lowering to 20°C.
8.13.3 Frost protection
If the controller is in mode Off or Manual and the outdoor temperature falls below a settable value,
a settable, minimum supply temperature will be maintained. Circulation pumps will be activated.
Frost protect.:Off
Outdoor temp activ.
Frost prot:0.0°C
Min sup. temp:10.0°C
8.13.4 Split of output signal
Any one of the temperature control output signals HS1, HS2, HS3, HWC1 or HWC2 can be split in
two.
Split of any
temp sequence:
No split