Corrigo E Heating manual, revision G Chapter 8 Configuration 33
Alarm text Pri Description
27 High cold water/hour B Cold water usage / hour higher than min. limit
28 High leakage B Leakage higher than set value
29 Malf. P1A&B-HS1 A Malfunction both circulation pumps P1A and P1B in
HS1
30 Malf. P1A&B-HS2 A Malfunction both circulation pumps P1A and P1B in
HS2
31 Malf. P1A&B-HS3 A Malfunction both circulation pumps P1A and P1B in
HS3
32 Pulse error CW1 B No pulses from cold water meter 1.
33 Pulse error CW2 B No pulses from cold water meter 2.
34 HS1 manual C HS1 in manual mode
35 HS2 manual C HS2 in manual mode
36 HS3 manual C HS3 in manual mode
37 HWC1 manual C HWC1 in manual mode
38 HWC2 manual C HWC2 in manual mode
39 Press. manual C Pressure control in manual mode
40 Boiler manual C Boiler in manual mode
41 P1A-HS1 manual C P1A-HS1 in manual mode
42 P1B-HS1 manual C P1B-HS1 in manual mode
43 P1A-HS2 manual C P1A-HS2 in manual mode
44 P1B-HS2 manual C P1B-HS2 in manual mode
45 P1A-HS3 manual C P1A-HS3 in manual mode
46 P1B-HS3 manual C P1B-HS3 in manual mode
47 P1-HWC1 manual C P1-HWC1 in manual mode
48 P1-HWC2 manual C P1-HWC2 in manual mode
49 P1-Freq. Manual C P1- frequency controlled in manual
50 HS1 Supply max B HS1 supply temp maximum limit activated
51 HS2 Supply max B HS2 supply temp maximum limit activated
52 HS3 Supply max B HS3 supply temp maximum limit activated
53 HS1 Supply min B HS1 supply temp minimum limit activated
54 HS2 Supply min B HS2 supply temp minimum limit activated
55 HS3 Supply min B HS3 supply temp minimum limit activated
56 HS1 Return max B HS1 return temp maximum limit activated
57 HS2 Return max B HS2 return temp maximum limit activated
58 HS3 Return max B HS3 return temp maximum limit activated
59 HS1 Return min B HS1 return temp minimum limit activated
60 HS2 Return min B HS2 return temp minimum limit activated
61 HS3 Return min B HS3 return temp minimum limit activated
62 HS1 Frost B HS1 frost protection active
63 HS2 Frost B HS2 frost protection active
64 HS3 Frost B HS3 frost protection active
65 Battery error B Malfunction of the internal memory-backup battery