35
Control units VCS
List of Data Points (HMI-SG controller)
Menu HMI-SG
Parameter
Meaning
Factory Settings
Notation Reading Value Min Max
code level code level
274 U Heat pump 0 no
1 variation A
2 variation B
275 U Type of gas heating 0 1 stage
1 2 stage
2 modulation
276 U Byppas damper gas heater 0 no
1 yes
277 U Cooling 0 no
1 water
2 1 step
3 2 step
4 inverter
5 inverter + 1 step
278 U Heat recovery 0 no
1 plate
2 wheel
3 glycol
279 U Mixing 0 no
1 yes
280 U Preheating 0 no
1 water
2 electric
281 U Extra heating 0 no
1 electric
282 U Temperature control mode 0 supply
1 cascade - room
2 cascade - return
283 U Humidity control mode 0 no
1 room
2 supply
3 cascade - room
Control parameters
Temperature start-up
301 A 302 U Cooling trigger temperature 30 -64 64 °C
303 A 304 U Heating trigger temperature 25 -64 64 °C
305 A 306 U Hysteresis 1 0.1 64 °C
307 A 308 U Heating and cooling blocking time 30 0 999 min
309 A 310 U Operating time 0 0 999 min
Night colling
311 A 312 U Temperature hysteresis 3 0 64 °C
313 A 314 U Minimum outdoor temperature setting 12 -64 64 °C
315 A 316 U Outdoor temperature and room temperature difference 5 1 64 °C
317 A 318 U Minimum night chilling operating time 30 0 999 min
Boost function
319 A 320 U Pre-set interval before time program start-up 60 0 999 min
321 A 322 U Temperature hysteresis 0.5 -64 64 °C
Required temperature compensation
323 A 324 U Cooling initial point (outdoor temperature) 25 -64 64 °C
325 A 326 U Cooling end point (outdoor temperature) 30 -64 64 °C
327 A 328 U Maximum cooling compensation (required value) 2 -64 64 dK
329 A 330 U Heating initial point (outdoor temperature) 5 -64 64 °C
331 A 332 U Heating end point (outdoor temperature) -20 -64 64 °C
333 A 334 U Maximum heating compensation (required value) -1 -64 64 dK
335 U Required cooling value current shi -64 64 °C
336 U Required heating value current shi -64 64 °C
Outdoor temperature dependent fan speed compensation
337 A 338 U Cooling initial point (outdoor temperature) 25 -64 64 °C