39
Control units VCS
List of Data Points (HMI-SG controller)
Menu HMI-SG
Parameter
Meaning
Factory Settings
Notation Reading Value Min Max
code level code level
List of Data Points (HMI-SG controller)
1 decrease
556 U Compensation display %
Humidity-dependent mixing damper position compensation
560 A 561 U Fan speed compensation function 0 Increase 0
1 Decrease
562 U Compensation display %
Control constants
Cooling factors (all versions)
601 S 602 A Proportional factor -5
603 S 604 A Integrating factor 60 s
605 S 606 A Derivative factor 0 s
Heat pump factors - heating
607 S 608 A Proportional factor 5
609 S 610 A Integrating factor 300 s
611 S 612 A Derivative factor 0 s
Heat pump factors - cooling
613 S 614 A Proportional factor -5
615 S 616 A Integrating factor 300 s
617 S 618 A Derivative factor 0 s
Room (outlet) temperature dependent fan speed compensation
619 S 620 A Proportional factor 20
621 S 622 A Integrating factor 0 s
623 S 624 A Derivative factor 0 s
Heating dependent fan speed compensation
625 S 626 A Proportional factor 5
627 S 628 A Integrating factor 120 s
629 S 630 A Derivative factor 0 s
Cooling dependent fan speed compensation
631 S 632 A Proportional factor -10
633 S 634 A Integrating factor 120 s
635 S 636 A Derivative factor 0 s
Air quality CO2 (VOC,CO) dependent compensation (damper position/
fan speed)
637 S 638 A Proportional factor -0.3
639 S 640 A Integrating factor 300 s
641 S 642 A Derivative factor 0 s
Mixing
643 S 644 A Proportional factor 7
645 S 646 A Integrating factor 45 s
647 S 648 A Derivative factor 15 s
Heat recovery RHE/BP PE
649 S 650 A Proportional factor 3
651 S 652 A Integrating factor 60 s
653 S 654 A Derivative factor 1 s
Heat recovery – antifreeze protection
655 S 656 A Proportional factor 20
657 S 658 A Integrating factor 150 s
659 S 660 A Derivative factor 0 s
Electric reheating
661 S 662 A Proportional factor 1
663 S 664 A Integrating factor 60 s
665 S 666 A Derivative factor 0 s
Electric pre-heating
667 S 668 A Proportional factor 5
669 S 670 A Integrating factor 120 s
671 S 672 A Derivative factor 0 s
Water heating with pre-heating function
673 S 674 A Proportional factor – AP from return water 20
675 S 676 A Integrating factor - AP from return water 90 s