EasyManua.ls Logo

Rheem IKONIC RTGH-SR11i - Page 61

Rheem IKONIC RTGH-SR11i
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IKONIC Tankless Water Heater Service Manual
61
2.2 ERROR CODE LIST
A063 ERROR CODE
Pump abnormality
If the water flow sensor does not detect water flow
when the recirculation pump is working, the water
heater displays the "A063 ” error code on the User In-
terface.
Diagnostic check
Recirculation Pump (Internal or external).
Turn Power OFF
Remove and reinsert connector "A" on the
control board and blue molex to connect to
pump.
Visually inspect for loose or damaged con-
nections.
Turn power ON and operate pump.
Unit has a loose connection.
Unit appears to be operating.
Check connector "A" and operate unit
again.
If "A063" error code returns, Replace
control board.
Measure DC voltage between #3 wire
(White) & #4 wire (Black) at connector
"A".
Replace pump (internal or external).
Is "A063" error
code appeared?
Is the voltage
108-132 DC
volts?
Yes
No
No
Yes
ERROR CODE DIAGNOSTICS

Table of Contents

Other manuals for Rheem IKONIC RTGH-SR11i

Related product manuals