EasyManua.ls Logo

Riello AARIA START - Page 17

Riello AARIA START
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INSTALLATION
17
A High pressure
B Low pressure
1 Nitrogen cylinder
2 Pressure regulator
3 Pressure gauge unit
4 3-way valve service connection
N2
AB
1
2
3
4
1 3-way valve service connection
1
charge the circuit with nitrogen through the service con-
nection on the 3-way shut-off valve
0
Do not use oxygen or acetylene or other flammable or poi-
sonous gases in the refrigerating circuit, as they can cause
explosions.
reach a pressure equal to 0.3 Mpa
wait 3 minutes.
check that the pressure has not dropped
reach a pressure equal to 1.5 Mpa
wait 3 minutes.
check that the pressure has not dropped
reach a pressure equal to 3 Mpa
adjust the reached pressure and room temperature
leave the circuit pressurised for 1 day
check that the pressure has not dropped
9
If the temperature has changed with respect to the noted
value consider that the pressure varied by 0.01 Mpa for 1 °C.
9
If pressure has dropped, detect the leak, fix it and repeat
the test.
9
To detect the leak, use a solution of water and soap and
check all the joints and welds, if any.
Having verified the absence of leakages:
create a pneumatic vacuum inside the circuit
Pneumatic vacuum
To create vacuum in the circuit:
keep the outdoor unit shut-off valves closed
A High pressure
B Low pressure
1 Pressure gauge unit
2 Vacuum pump
3 3-way valve service connection
AB
1
2
3
connect the vacuum pump to the pressure gauge unit
connect the pressure gauge unit to the service connection
on the 3-way shut-off valve
completely close the pressure reducing valve of the pres-
sure gauge
fully open the low pressure valve of the pressure gauge unit
let the vacuum pump work for at least 15 minutes
reach a pressure that is close to -0.1 Mpa
close the low pressure valve of the pressure gauge unit
switch off the vacuum pump
wait 5 minutes
check that the pressure has not risen again
If the pressure has risen again:
1 2-way shut-off valve
2 On-off valve cover plug
3 Hex wrench
A Opening by 1/4 of a turn
A
3
1
2
open the 2-way shut-off valve by a quarter of a turn
close it after 6 seconds so as to allow a small quantity of
refrigerant into the circuit
detect the leak using a solution of water and soap
fix the leak
recreate the pneumatic vacuum
9
Take the necessary safety precautions for the system refrig-
erant.
9
It is forbidden to carry out welding operations with refrig-
erant inside the cooling circuit. If necessary, the refrigerant
must be recovered and the circuit must be cleaned with ni-
trogen without oxygen.
0
It is forbidden to use detergents containing chlorine be-
cause it could react with the refrigerant and corrode the
copper pipes.

Related product manuals