EasyManua.ls Logo

Riello AARIA START - Page 16

Riello AARIA START
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INSTALLATION
16
Pipe insulation
Connection pipes must be thermally insulated to prevent dis-
persions of heat or formation of condensate.
1 Gas pipe
2 Condensation discharge
3 Liquid pipe
4 Heat insulation
5 Adhesive tape
5
4
4
1
2
3
insulate the liquid and gas pipes separately
use insulating material that is thicker than 15 mm
ensure that the insulating material adheres to the pipe
without gaps
fix using adhesive tape
9
Do not tighten the adhesive tape excessively to prevent
damaging the insulation.
9
Avoid partial insulation of the pipes.
9
In case of use with outdoor temperature above 30 °C and
relative humidity above 80%, increase wall thickness up to
20 mm.
For gas pipes:
ensure that the material used resists to temperatures up
to 120°C
For liquid pipes:
ensure that the material used resists to temperatures up
to 70°C
Stop valves
Cooling connections feature shut-off valves.
During operations on the cooling circuit, start-up and service, it
may be required to open and close the valves.
A Opening
B Closing
1 Service connection blanking plug
2 On-off valve shaft
3 Refrigerating pipe attachment
4 On-off valve cover plug
5 Hex wrench
1
2
3
4
5
AB
If required:
remove the valve covering plug
operate on the valve shaft with an hex wrench
open or close according to what is needed
immediately stop as soon as the valve shaft has reached
the stop point
use a torque wrench calibrated on the valve diameter
Pipe Ø
Hex
wrench
Valve
tightening
torque
Plug
tightening
torque
mm inches mm Nm Nm
6,35 1/4 5 6 25
9,52 3/8 5 6 25
12,70 1/2 5 8 30
15,88 5/8 5 10 35
9
Do not force beyond the stop point to prevent damaging the
shaft and causing leakage as a consequence.
At the end of the operations:
refit the valve covering plug
9
Carefully check for absence of leakages from the closing
point of the plug.
Circuit tightness check
The appliance is tested at the factory and the indoor refrigerat-
ing circuit tightness does not usually need to be checked.
The refrigerating circuit built on site needs to be checked instead.
To check tightness:
keep the outdoor unit shut-off valves closed

Related product manuals