11
PRODUCT DESCRIPTION
Unit AR 1000 AR 1500 AR 2000
Max operating temperature
°F 194 194 194
(°C) (90) (90) (90)
Max HE allowable temperature
°F 210 210 210
(°C) (98.9) (98.9) (98.9)
Ambient storage temperature
°F 5 to 158 5 to 158 5 to 158
(°C) (-15 to 70) (-15 to 70) (-15 to 70)
Ambient functioning temperature
°F 32 to 120 32 to 120 32 to 120
(°C) (0 to 49) (0 to 49) (0 to 49)
Max Ambient Functioning Humidity
°F 95 % at 104 95 % at 104 95 % at 104
(°C) 95 % at 40 95 % at 40 95 % at 40
Surface heat exchanger per module
SQFT 43 43 43
(m
2
) (4) (4) (4)
Standard Listings & Approvals ETL, ASME, AHRI, CSD-1, SCAQMD
Electrical Req. 120V/1Ph/60Hz / 15.5 FLA** 120V/1Ph/60Hz / 23.3 FLA** 230V/1Ph/60Hz / 15.5 FLA**
Weight (dry)
lbs 1058 1323 1676
(kg) (480) (600) (760)
Dimension W x H x D
Inch 33.3X67.2X60.8 *** 33.3X67.2X60.8 *** 33.3X83X60.8 ***
(mm) (845X1707X1544) (845X1707X1544) 845X2108X1544)
(**) FLA (Full Load Amperage) – maximum current drawn by the boiler if all pumps reach rated horsepower
(***) Mounting feet may be removed during installation to reduce the overall height by 2”. Feet must be re-installed once boiler is in
its nal installation location.