APPENDIX
Menu item Sub item / Parameter Range Default Value Units User level
(52) DHW Instant PID I 0…1255 160 3: Factory
(53) DHW Instant PID D 0…1255 0 3: Factory
(60) Flow Rate Start 0.1…20 1.4 l/min 3: Factory
(61) Flow Rate Lo Temp Pwr 0.1…20 1.4 l/min 3: Factory
(62) Flow Rate Hi Temp Pwr 0.1…20 1.4 l/min 3: Factory
(63) DHW On Off Period 10…60 30 Sec. 3: Factory
(64) PreHeat Mode Off, Comfort, Eco, Anti-Fr Off 1: User
(65) PreHeat Eco Setpoint 20...60 (68...140) 30 (86) °C (°F) 3: Factory
(67) PreHeat After Tap Hld Time 0…255 30 Sec. 3: Factory
(68) After Tap Hold Time 0…255 120 Sec. 3: Factory
(69) PreHeat Hyst Down 0...30 (0...54) 5 (9) °C (°F) 3: Factory
(70) PreHeat Hyst Up 0...30 (0...54) 0 (0) °C (°F) 3: Factory
(71) PreHeat Delay Time 0…15 10 Sec. 3: Factory
(92) Fan Speed Maximum 0…12750 6900 RPM 2: Installer
(93) Fan Speed Minimum 0…12750 1900 RPM 2: Installer
(94) Fan Speed Ignition 0…12750 4500 RPM 2: Installer
(116) Prog. Input 1.
0) Disabled
1) Water pressure sensor
2) CH ow switch
3) Flue pressure switch
Managing: 3
Dependent: 3
2: Installer
(117) Prog. Input 2.
0) Disabled
1) DHW ow sensor
2) DHW ow switch
3) CH ow sensor
Managing: 3
Dependent: 3
2: Installer
(118) Prog. Input 3.
0) Disabled
1) Drain switch
2) Gas pressure switch
Managing: 2
Dependent: 0
2: Installer
(119) Prog. Input 4.
0) Supply 2 sensor
1) Disabled
2) Air Damper Switch
Managing: 1
Dependent: 1
2: Installer
(120) Prog. Input 5.
0) Disabled
1) T_Return sensor
2) Extern switch
Managing: 1
Dependent: 1
2: Installer
(121) Prog. Input 6.
0) Disabled
1) T_Flue sensor
2) Flue switch
3) APS switch
Managing: 1
Dependent: 1
2: Installer
(122) Prog. Input 7.
0) Disabled
1) T_Flue_2 sensor
2) T_Flue_2 + Bl. Flue
3) T_System sensor
4) Blocked Flue switch
5) Cascade Sensor
Managing: 3
Dependent: 5
2: Installer
(123) Prog. Input 8.
0) Disabled
1) T_DCW sensor
2) Water pressure switch
Managing: 2
Dependent: 0
2: Installer
(188) Progr. Input 9.
0) Disabled
1) DHW sensor
2) Zone sensor
Managing: 1
Dependent: 1
2: Installer
(124) Prog. Input RT.
0) Disabled
1) Enabled
1 2: Installer
(*) LWCO1 NA
Managing: 1
Dependent: 0
2: Installer
(**) LWCO2 NA
Managing: 2
Dependent: 2
2: Installer

Table of Contents