108
ENGLISH
7KHWDUJHWRXWOHWZDWHUWHPSHUDWXUHGXULQJÀRRUGU\LQJXSGHVFULEHGLQ
the picture below:
t_DRYUP
t_HIGHPEAK
T1S
t
t_DRYD
T_DRYPEAK
10.5.13 AUTO RESTART
The AUTO RESTART function is used to select whether the unit reap-
plies the user interface settings at the time when power returns after a
power supply failure.
Go to "
"> FOR SERVICEMAN>13.AUTO RESTART
13 AUTO RESTART
YES
NON
ADJUST
13.1 COOL/HEAT MODE
13.2 DHW MODE
The AUTO RESTART function reapplies the user interface settings at
the time of the power supply failure. If this function is disabled, when
power returns after a power supply failure, the unit won’t auto restart.
10.5.14 POWER INPUT LIMITATION
How to set the POWER INPUT LIMITATION
Go to "
"> FOR SERVICEMAN>14.POWER INPUT LIMITATION.
14 POWER INPUT LIMITATION
0
ADJUST
14.1 POWER LIMITATION
Power limitation (N°)
012345678
Model
18kW1818171615141312,512
22kW212120191817161514
26kW242423222120191817
30kW282827262524232221
10.5.15 INPUT DEFINE
How to set the INPUT DEFINE
Go to "
"> FOR SERVICEMAN> 15.INPUT DEFINE
15 INPUT DEFINE
HMI
-2°C
NO
10m
NO
15.6 Ta
15.7 Ta-adj
15.8 INPUT SOL.
15.9 LF-PIPE LENGTH
15.10 RT/Ta_PCB
15 INPUT DEFINE
REMOTE
NO
NO
NO
HMI
15.1 M1M2
15.2 SMART GRID
15.3 Tw2
15.4 Tbt1
15.5 Tbt2
15 INPUT DEFINE
NO
15.11 PUMP I SILENT MODE
15.12 DFT1/DFT2
DEFROST
10.5.16 CASCADE SET
How to set the CASCADE SET
Go to "
">FOR SERVICEMAN>16.CASCADE SET.
16 CASCADE SET
10%
5 MIN
0
16.1 PER START
16.2 TIME_ADJUST
16.3 ADDRESS RESET
After setting the address, you need to press NH\WRFRQ¿UP7KH
address “FF” is an invalid address code.
10.5.17 HMI ADDRESS SET
How to set the HMI ADDRESS SET
Go to "
">FOR SERVICEMAN>17.HMI ADDRESS SET.
17 HMI ADDRESS SET
17.1 HMI SET
17.2 HMI ADDERSS FOR BMS
MASTER
1
17.3 STOP BIT
1
When HMI SET is set to SLAVE, the controller can only switch the ope-
UDWLRQPRGHWXUQRQRURႇVHWWKHWHPSHUDWXUHDQGFDQQRWVHWRWKHU
paramters and functions.
The address “FF” is an invalid address code.