Fan Convector Manual 11
FinalChecklist
□ The heater is not subject to corrosive compounds in the air.
□ Clearances from the heater are met.
□ The unit is not installed above 5,200.
□ The unit has been properly calibrated for the appropriate altude.
□ A manual gas control valve has been placed in the gas line to the heater.
□ Check the gas lines and connecons for leaks.
□ Confirm that the gas inlet pressure is within limits.
□ Confirm that the heater is rated for the gas type supplied.
□ Confirm that the electricity is supplied from a 120 VAC, 60 Hz power source, is in a properly grounded circuit,
and turned on.
□ Explain to the customer the importance of not blocking the warm air discharge.
□ Explain to the customer the operaon of the heater, safety guidelines, maintenance, and warranty.
□ The installaon must conform with local codes or, in the absence of local codes, with the Naonal Fuel Gas
Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Installaon Code, CSA B149.1. If installed in a
manufactured home, the installaon must conform with the Manufactured Home Construcon and Safety
Standard, Title 24 CFR, Part 3280 and/or CAN/SCA Z240 MH Series, Mobile Homes.
□ The heater must not be installed in a confined space or unusually ght construcon unless provisions are
provided for adequate combuson and venlaon air.
□ The appliance is not installed in a bedroom or bathroom.
□ Leavetheenremanualtapedtotheheaterorgivetheenremanualdirectlytotheconsumer.