EasyManua.ls Logo

Rittal Blue e+ - Page 26

Rittal Blue e+
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 Installation
EN
26 Rittal roof-mounted Blue e+ cooling unit/VX25 Blue e+ integration solution
The units are high-voltage tested ex works. An addi-
tional high voltage test must only be carried out with a
DC voltage supply source (1500 VDC max.).
If the combined output of the frequency converters,
power converters or transformers in the network
where the device is being operated is >70 kVA, the
customer must connect a Class II surge voltage pro-
tector in the mains supply line upstream of the cooling
unit. The surge voltage protector must be designed to
EN 61800 -1. The following values may be assumed
as starting-points for the design:
Three-phase devices
There is no need to observe a counterclockwise or
clockwise phase rotation when making the electrical
connection for inverter devices in the three-phase ver-
sion. The electronics incorporated into the devices au-
tomatically create the required phase rotation.
In three-phase devices, the absence of a phase is de-
tected, and the device is switched off.
Outgoing equipment is monitored by the inverter, and
deactivated in the event of a malfunction in the elec-
tricity supply.
Door limit switch
Each door limit switch can only be assigned to one
cooling unit.
Several door limit switches may be operated in parallel
with one cooling unit.
The minimum cross-section for the connection cable
is 0.3 mm² for a cable length of 2 m.
The line resistance to the door limit switch must not
exceed a maximum of 50 Ω.
The maximum admissible line length is 10 m.
The door limit switch only supports a floating connec-
tion; no external voltages.
The contact of the door limit switch must be closed
when the door is open.
The safety extra-low voltage for the door limit switch is
provided by the internal power pack: Current approx.
5mA DC.
Connect the door limit switch to terminals 5 and 6 of
the signal connector.
Fig. 13: Fasteners at the bottom of the roof-mounted cooling
unit
Key
1 T-rail for strain relief
2 Connection for mains connector (X1)
3 Connection for IoT interface 3124.300 (X3)
4 Connection for signal connector (X2)
Potential equalisation
If, for EMC reasons, the unit is to be integrated into the
customer's existing potential equalisation system, a
conductor may be connected to the potential equalisa-
tion connection point. The connection point is labelled
with the required switch symbol.
Fig. 14: Connection point for potential equalisation
Key
1 Connection point M6
Attach the potential equalisation to the unit's connec-
tion point using the screw, washer and contact wash-
er.
Transformers,
power electronics
Assumed discharge
energy
70 kVA…100kVA 40J
100 kVA…200kVA 80J
200 kVA…400kVA 160J
400 kVA…800kVA 320J
Tab. 4: Design of the surge voltage protector
Note:
The door limit switch is installed in the enclo-
sure as standard for the integration solution.
Consequently, the following description ap-
plies only to the Blue e+ roof-mounted cool-
ing unit.
1
2
4
3
1

Table of Contents

Related product manuals