13 Technical specifications
EN
68 Rittal Liquid Cooling Package
13 Technical specifications
13.1 30 kW versions
13.1.1 LCP Rack and LCP Inline
Technical specifications
Description/Model No. TopTherm LCP Rack 30 CW / 3311.138 (1000 mm depth)
Description/Model No. TopTherm LCP Rack 30 CW / 3311.238 (1200 mm depth)
Description/Model No. TopTherm LCP Inline 30 CW / 3311.538 (1200 mm depth)
Dimensions and weight
Dimensions width x height x depth (mm) 300 x 2000 x 1000 (3311.138) or 1200 (3311.238/538)
Usable U 42
Weight, max. [kg] 220
Electrical connection
Type of electrical connection Connector
Rated voltage [V, Hz] 208/2~ 50/60 230/1~ 50/60
Rated current [A] (1 fan) 2.3 2.0
Max. current [A] (6 fans) 13.5 12.3
Pre-fuse [A] (6 fans) 20 20
Duty cycle [%] 100
Protection category IP 20
Cooling output
Number of fans 1 2
Cooling output [kW] 10 20
Power consumption P
el
[kW] 0.47 0.65
Air throughput, max. [m
3
/h] 4800
Cooling circuit
Cooling medium Water (see Internet for specifications)
Coolant inlet temperature [°C] +15
PO
H2O
[bar (psi)] 2 to 6 (29 to 88)
PS
H2O
[bar (psi)] 6 (88)
PT
H2O
[bar (psi)] 12 (175)
Fill quantity [l] 7
Water connection 1½" outer thread