13 Technical specifications
EN
68 Rittal Liquid Cooling Package
13 Technical specifications
13.1 30 kW versions
13.1.1 LCP Rack and LCP Inline
Technical specifications
Description/Model No. TopTherm LCP Rack 30 CW / 3311.138 (1000 mm depth)
Description/Model No. TopTherm LCP Rack 30 CW / 3311.238 (1200 mm depth)
Description/Model No. TopTherm LCP Inline 30 CW / 3311.538 (1200 mm depth)
Dimensions and weight
Dimensions width x height x depth (mm) 300 x 2000 x 1000 (3311.138) or 1200 (3311.238/538)
Usable U 42
Weight, max. [kg] 220
Electrical connection
Type of electrical connection Connector
Rated voltage [V, Hz] 208/2~ 50/60 230/1~ 50/60
Rated current [A] (1 fan) 2.3 2.0
Max. current [A] (6 fans) 13.5 12.3
Pre-fuse [A] (6 fans) 20 20
Duty cycle [%] 100
Protection category IP 20
Cooling output
Number of fans 1 2
Cooling output [kW] 10 20
Power consumption P
el
[kW] 0.47 0.65
Air throughput, max. [m
3
/h] 4800
Cooling circuit
Cooling medium Water (see Internet for specifications)
Coolant inlet temperature [°C] +15
PO
H2O
[bar (psi)] 2 to 6 (29 to 88)
PS
H2O
[bar (psi)] 6 (88)
PT
H2O
[bar (psi)] 12 (175)
Fill quantity [l] 7
Water connection 1½" outer thread

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rittal TopTherm LCP Rack CW and is the answer not in the manual?

Rittal TopTherm LCP Rack CW Specifications

General IconGeneral
BrandRittal
ModelTopTherm LCP Rack CW
CategoryCooling boxes
LanguageEnglish

Related product manuals