3. COMMUNICATION INITIAL IDENTIFIER
IMCB04-E10
29
6
0: No option function provided (No optional function provided)
1: RUN/STOP function provided
4: Communication function provided (RKC standard communication)
5: Communication function provided (RKC standard communication), RUN/STOP function
provided
6: Communication function provided (MODBUS communication)
7: Communication function provided (MODBUS communication), RUN/STOP function provided
8: Self-tuning provided
9: Self-tuning provided, RUN/STOP function provided
12: Self-tuning provided, Communication function provided (RKC standard communication)
13: Self-tuning provided, Communication function provided (RKC standard communication),
RUN/STOP function provided
14: Self-tuning provided, Communication function provided (MODBUS communication)
15: Self-tuning provided, Communication function provided (MODBUS communication),
RUN/STOP function provided
Do not set 2, 3, 10 or 11. Malfunction may result.
7
0: No alarm
1: Alarm 1 (SV high alarm)
3: Alarm 1 (SV low alarm)
4: Alarm 2 (SV high alarm)
5: Alarm 1 (SV high alarm), alarm 2 (SV high alarm)
7: Alarm 1 (SV low alarm), alarm 1 (SV high alarm)
12: Alarm 2 (SV low alarm)
13: Alarm 1 (SV high alarm), alarm 2 (SV low alarm)
15: Alarm 1 (SV low alarm), alarm 2 (SV low alarm)
Do not set 2, 6, 8, 9, 10, 11 or 14. Malfunction may result.

Other manuals for RKC INSTRUMENT CB100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the RKC INSTRUMENT CB100 and is the answer not in the manual?

RKC INSTRUMENT CB100 Specifications

General IconGeneral
BrandRKC INSTRUMENT
ModelCB100
CategoryController
LanguageEnglish

Related product manuals