24 IMCB04-E10
3. COMMUNICATION INITIAL
List of Communication Initialize Identifiers
Note that there are identifiers which cannot be communicated depending on the
specification.
The number of digits is 6 for all data.
For details on the structure of communication data, see the CB100/CB400/CB500/CB700/CB900
Communication Instruction Manual (IMCB03-E).
ID: Identifier (RO: Read only R/W: Read/write)
Name ID Data range Factory
set value
R/W
Initialization mode selection IO 0: RO 1: R/W 0 R/W
Setting necessary code [Cod] IP 0 to 2 0 R/W
Input type selection [SL1] XI 0 to 15
1
To vary
depending on
the
specification
R/W
Engineering unit and cooling type
selection [SL2]
XQ 0: °C (Air cooling)
1: °F (Air cooling)
2: °C (Water cooling)
3: °F (Water cooling)
To vary
depending on
the
specification
R/W
Heater break alarm (HBA),
control loop break alarm (LBA),
special specification, or
control loop break alarm (LBA)
output selection [SL3]
LV 0: No function provided
1: HBA provided
2: LBA provided, LBA is output
from alarm 1
5: HBA (Z-132 specification)
provided
10: LBA provided, LBA is
output from alarm 2
To vary
depending on
the
specification
R/W
Alarm 1 (ALM1) type or
Alarm 1 (ALM1) with hold action
selection [SL4]
XA 0 to 15
2
To vary
depending on
the
specification
R/W
Alarm 2 (ALM2) type or
Alarm 2 (ALM2) with hold action
selection [SL5]
XB 0 to 15
2
To vary
depending on
the
specification
R/W
Continued on the next page.