3. SETTING FOR COMMUNICATION
IMCD06-E2
11
3.5 Data construction setting
Set the data bit construction during communication by using numerals from 0 to 5. Press the UP or
DOWN key to change the numeral.
Symbol
Name
Setting range
Description
Factory set
value
Data construction 0 to 5
See *A
Selects data construction
during communication.
0
bIT
*A
Setting Data bit [bit] Parity bit Stop bit [bit]
0 8 None 1
1 8 None 2
2 7 Even 1
3 7 Even 2
4 7 Odd 1
5 7 Odd 2
Set the same data construction to both the controller and connecting host computer.
When the communication parameter was changed, always turn on the power again.
Otherwise, no communication is performed by using the changed value.
If key operation is not performed for more than 1 minute without pressing the SET key
after the device address is set, the controller is automatically changed to PV/SV display
mode. In this case, the set data construction returns to the value before the setting is
changed.